Protectowire 2000 FireSystem Specifikace Strana 47

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 63
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 46
~ 44 ~
%@D9?>L&M1DD5BI81B75B)D1DEC#5D5BC
)(&*%$
An available numerical indication of battery status may be provided with Battery Charger Status Meters. These meters supply an
easy-to-read accurate display of both the charger current draw and the charging/standby voltage level.
%&(*%$
The ammeter continuously displays battery charger current draw. This level may be between 1.250 amps and 0.012 amps (trickle
current), depending on the present charge state of the batteries. The voltmeter 4?5C>?D continually monitor the charger voltage
level. Depress the Voltmeter Read Switch to read the voltage level of the batteries. While in standby “AC. ON” mode, the voltage
level reflects the battery set and charger levels in a charging state. While in “AC. OUT” mode, the voltage level reflects the actual
standby battery set voltage level.
,?<D=5D5B
,?<D=5D5B(514)G9D38
==5D5B
%@D9?>L'M*9=55<1I(5<1I
)(&*%$
A time delay relay is employed to prolong the activation of a desired control function within the FS2000 Control Panel. This delay
to operate a device provides an adjustable timing (fixed also available) cycle for field trimming ease.
%&(*%$
Normally the time delay relay positive leg is sourced with 24VDC and the negative leg is connected to a low going zone output.
Once the appropriate output is activated, the relay coil is energized and the timer cycle begins. After this cycle times out (com-
pletes), the relay contacts change state and activate the desired control function. This device is usually self resetting once the out-
put activating it is reset or cleared. Rotate the timer adjustment knob to adjust the timing cycle or duration to the desired setting.
Please reference the Installation Wiring Diagram for specific wiring and activation schemes.
*9=5B
4:ECD=5>D
"*("
"*("
Voltmeter Range 0-30 VDC +/- 5%
Ammeter Range 0-5.0 amps +/- 5%
Contact Rating 10 Amp @ 120VAC Resistive
Coil 24 VDC @ 0.125 Amp
Time Delay 0.6 - 60 Seconds
Other Time Delays are also available on special order